Q
The AccuLoad unit is not counting and there is no product flow.


A
Be sure no manual valves are closed upstream of the meter. Be sure the strainer is clean. If the first two items check out, then the problem is the valve, which is not opening. Check the voltage to the solenoids, remove and check the solenoid operation. Remove the cover of the valve and be sure the diaphragm does not have a hole in it.

If, after following these steps, you need more information, contact us.


Q
The AccuLoad won't go into program mode and the display does not blank when enter is pressed twice.


A
Try to get into the program mode on one side only then run the key pad diagnostic to confirm that the keys are working.

If the program mode cannot be entered on either side, measure the voltage at the program and weights and measures inputs. If voltage is present, then replace the I/O board. If voltage is not present, check the wiring and the switches.

If, after following these steps, you need more information, contact us.